American Wire Gauge table and AWG Electrical Current Load Limits
| AWG gauge
|
Diameter Inches
|
Diameter mm
|
Ohms per 1000 ft
|
Maximum amps for chassis wiring
|
| 1
|
0.2893
|
7.34822
|
0.1239
|
211
|
| 2
|
0.2576
|
6.54304
|
0.1563
|
181
|
| 3
|
0.2294
|
5.82676
|
0.197
|
158
|
| 4
|
0.2043
|
5.18922
|
0.2485
|
135
|
| 5
|
0.1819
|
4.62026
|
0.3133
|
118
|
| 6
|
0.162
|
4.1148
|
0.3951
|
101
|
| 7
|
0.1443
|
3.66522
|
0.4982
|
89
|
| 8
|
0.1285
|
3.2639
|
0.6282
|
73
|
| 9
|
0.1144
|
2.90576
|
0.7921
|
64
|
| 10
|
0.1019
|
2.58826
|
0.9989
|
55
|
| 11
|
0.0907
|
2.30378
|
1.26
|
47
|
| 12
|
0.0808
|
2.05232
|
1.588
|
41
|
| 13
|
0.072
|
1.8288
|
2.003
|
35
|
| 14
|
0.0641
|
1.62814
|
2.525
|
32
|
| 15
|
0.0571
|
1.45034
|
3.184
|
28
|
| 16
|
0.0508
|
1.29032
|
4.016
|
22
|
| 17
|
0.0453
|
1.15062
|
5.064
|
19
|
| 18
|
0.0403
|
1.02362
|
6.385
|
16
|
| 19
|
0.0359
|
0.91186
|
8.051
|
14
|
| 20
|
0.032
|
0.8128
|
10.15
|
11
|
|
| AWG gauge
|
Diameter Inches
|
Diameter mm
|
Ohms per 1000 ft
|
Maximum amps for chassis wiring
|
| 21
|
0.0285
|
0.7239
|
12.8
|
9
|
| 22
|
0.0254
|
0.64516
|
16.14
|
7
|
| 23
|
0.0226
|
0.57404
|
20.36
|
4.7
|
| 24
|
0.0201
|
0.51054
|
25.67
|
3.5
|
| 25
|
0.0179
|
0.45466
|
32.37
|
2.7
|
| 26
|
0.0159
|
0.40386
|
40.81
|
2.2
|
| 27
|
0.0142
|
0.36068
|
51.47
|
1.7
|
| 28
|
0.0126
|
0.32004
|
64.9
|
1.4
|
| 29
|
0.0113
|
0.28702
|
81.83
|
1.2
|
| 30
|
0.01
|
0.254
|
103.2
|
0.86
|
| 31
|
0.0089
|
0.22606
|
130.1
|
0.7
|
| 32
|
0.008
|
0.2032
|
164.1
|
0.53
|
| 33
|
0.0071
|
0.18034
|
206.9
|
0.43
|
| 34
|
0.0063
|
0.16002
|
260.9
|
0.33
|
| 35
|
0.0056
|
0.14224
|
329
|
0.27
|
| 36
|
0.005
|
0.127
|
414.8
|
0.21
|
| 37
|
0.0045
|
0.1143
|
523.1
|
0.17
|
| 38
|
0.004
|
0.1016
|
659.6
|
0.13
|
| 39
|
0.0035
|
0.0889
|
831.8
|
0.11
|
| 40
|
0.0031
|
0.07874
|
1049
|
0.09
|
|
|
|
|
|